Gas-Insulated Switchgear

Gas-Insulated Switchgear

  • For the distribution of electrical power, CPEPEC offers various gas-insulated switchgear types, which can be used in transformer and distribution systems of power grid and power plant, as well as in industrial medium-voltage systems, e.g. mining industry, petrifaction & metallurgy industry.

  • In all these applications, gas-insulated switchgear technology from CPEPEC provides exceptional advantages in respect of climatic independence, personal safety and maintenance-free design. For the customer, this offers the high benefit of maximum supply reliability in his network, both as a provider of customers and as an energy supplier for production processes.

  • Fixed-mounted circuit-breaker switchgear is indoor, factory-assembled, type-tested, single-pole metal-enclosed, gas-insulated switchgear with metallic partitions, for single-busbar and double-busbar applications, as well as for traction power supply systems.

Products Information

  • Up to 40.5 kV, 40 kA (3s), 5000 A busbar, feeder 3150 A

  • Metal-enclosed

  • Single-busbar System

  • Gas-insulated

  • Hermetically enclosed

  • Factory-assembled, routine-tested according IEC 62 271-200

  • Type-tested according IEC 62 271-200

 

Features

  • Compact, maintenance-free and climate-independent

  • Security of Operation, Reliability

  • Personal Safety

  • Environmental Independence

  • Compactness

  • Maintenance-free Design

  • Cost-efficient, Ecological 

NO.

Title

Unit

XGN-12

XGN-24

XGN-27.5

XGN-40.5

1

Rated voltage

KV

12

24

27.5

40.5

2

Rated power frequency withstand voltage 

KV

65

65

110

120

3

Rated lightning impulse withstanding voltage

KV

125

125

250

220

4

Rated frequency

Hz

50, 60

50, 60

50, 60

50, 60

5

Rated short circuit breading current

KA

40

31.5

31.5

20, 25, 31.5

6

Rated short-time withstand current duration

KA

40

31.5

31.5

20, 25, 31.5

7

Rated peak withstand current(max)

KA

100

80

80

50, 63, 80

8

Duration of short-time withstand current duration

S

4

4

4

4

9

Rated current

A

2000

2500

3150

630, 1250, 1600, 2000, 2500

10

Circuit breaker mechanical life

Times

20000

20000

20000

30000

11

Rated inflation pressure

Mpa

0.03

0.03

0.05

0.04

12

Insulating gas type

 

N2/SF6

N2/SF6

SF6

SF6

13

Annual leakage rate

 

<0.1%

<0.1%

<0.1%

<0.1%

14

5min power frequency withstand voltage at zero gauge pressure

KV

65

65

95

95

15

Sulfur hexafluoride gas moisture content 2 ℃

ppm

≤500

≤500

≤500

≤500

16

Gas chamber partial discharge amount 0

pC

≤50

≤50

≤50

≤50

17

Dimensions

mm

600X485X2400

(600, 800)X1485X2400*

18

Protection level

Inflatable housing

 

IP67

Low pressure compartment

 

IP3X、IP4X、IP44、IP5X


19

Internal fault arc withstand test

 

31.5KA/0.5S

31.5KA/1S

     